Brochure

12
Code Function Name Setting Range
Setting During
Operation
(allowed or not)
Change During
Operation
(allowed or not)
Default
Setting
Monitor mode
d001 Output frequency monitoring 0.00 to 99.99 / 100.0 to 400.0 [Hz]
d002 Output current monitoring 0.0 to 655.3 [A]
d003 Rotation direction minitoring F (Forward) / o (Stop) / r (Reverce)
d004 Process variable (PV), PID feedback monitoring
0.00 to 99.99 in steps of 0.01/100.0 to 999.9 in steps of 0.1/1000. to 9999. in steps of 1/
1000 to 9999 in steps of 10/
100 to 999 in units of 1000
d005 Intelligent input terminal status
(Example)
7, 5, 3, 1: ON
6, 4, 2 : OFF
ON
OFF
d006 Intelligent output terminal status
(Example)
11 : ON
AL, 12 : OFF
ON
OFF
d007 Scaled output frequency monitoring 0.00 to 99.99 / 100.0 to 999.9 / 1000. to 9999./ 1000 to 3999
d008 Actual-frequency monitoring -400. to -100. / -99.9 to -10.0 / -9.99 to -0.00 / 0.00 to 99.99 / 100.0 to 400.0 [Hz]
d009 Torque command monitoring -200 to +200 [%]
d010 Torque bias monitoring -200 to +200 [%]
d012 Torque monitoring -200 to +200 [%]
d013 Output voltage monitoring 0.0 to 600.0 [V]
d014 Power monitoring 0.0 to 999.9 [kW]
d015 Cumulative power monitoring
0.0 to 999.9 in steps of 1 kW/h, or the unit set for function "b079"/
1000 to 9999 in units of 10 kW/h, or the unit set for function "b079"/
100 to 999 in units of 1000 kW/h, or the unit set for function "b079"
d016 Cumulative operation RUN time monitoring
0. to 9999. in units of 1 hour / 1000 to 9999 in units of 10 hours / 100 to 999 in units of 1,000 hours
d017 Cumulative power-on time monitoring
0. to 9999. in units of 1 hour / 1000 to 9999 in units of 10 hours / 100 to 999 in units of 1,000 hours
d018 Heat sink temperature monitoring -20.0 to 150.0 [ ºC]
d022 Life-check monitoring
1: Capacitor on
main circuit board
2:cooling-fan
Lifetime expired
Normal
d023 EzSQ program counter 0 to 1024
d024 EzSQ program number 0000 to 9999
d025 User monitor 1 -2147483647 to 2147483647
d026 User monitor 2 -2147483647 to 2147483647
d027 User monitor 3 -2147483647 to 2147483647
d029 Position setting monitor -268435455 to 268435455
d030 Position feedback monitor -268435455 to 268435455
d050 Dual monitor Displays two different data congured in b160 and b161.
d060 Inverter mode monitor Displays currently selected inverter mode : I-C / I-V
d080 Trip Counter 0. to 9999. in units of 1 trip / 1000 to 6553 in units of 10 trips
d081 d086
Trip info. 1–6 (factor) Factor code
d090 Warning monitor Warning code
d102 DC voltage monitoring (across P and N) 0.0 to 999.9 / 1000. [V]
d103 BRD load factor monitoring 0.0 to 100.0 [%]
d104 Electronic thermal overload monitoring 0.0 to 100.0 [%]
Setting mode
F001 Output frequency setting 0 / "start frequency" to "maximum frequency" [Hz] 0.00
F002 Acceleration (1) time setting 0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s] 10.00
F202 Acceleration (1) time setting, 2nd motor 0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s] 10.00
F003 Deceleration (1) time setting 0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s]
10.00
F203 Deceleration (1) time setting, 2nd motor 0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s] 10.00
F004 Keypad Run key routing 00 (Foward) / 01 (Reverce) × × 00
Basic settings
A001 Frequency source setting
00 (keypad potentiometer) / 01 (control circuit terminal block) / 02 (digital operator) / 03 (Modbus) /
04 (option) / 06 (pulse train input) / 07 (easy sequence) / 10 (operation function result)
× × 02
A201 Frequency source setting, 2nd motor × × 02
A002 Run command source setting
01 (control circuit terminal block) / 02 (digital operator) /
03 (Modbus) / 04 (option)
× × 02
A202 Run command source setting, 2nd motor × × 02
A003 Base frequency setting 30.0 to "maximum frequency (1st)" [Hz] × × 60
A203 Base frequency setting, 2nd motor 30.0 to "maximum frequency (2nd)" [Hz] × × 60
A004 Maximum frequency setting
"Base frequency (1st)" to 400.0 [Hz]
× × 60
A204 Maximum frequency setting, 2nd motor × × 60
Analog input setting
A005 [AT] selection
00 (switching between O and OI terminals) /
02 (switching between O terminal and keypad potentiometer) /
03 (switching between OI terminal and keypad potentiometer)
× × 00
A011 Pot./O-L input active range start frequency 0.00 to 99.99/100.0 to 400.0 [Hz] × 0.00
A012 Pot./O-L input active range end frequency 0.00 to 99.99/100.0 to 400.0 [Hz] × 0.00
A013 Pot./O-L input active range start voltage 0 to 100 [%] × 0
A014 Pot./O-L input active range end voltage 0 to 100 [%] × 100
A015 Pot./O-L input start frequency enable 00 (A011) / 01 (0Hz) × 01
A016 External frequency lter time constant 1 to 30 / 31 × 8
A017 Easy sequence function selection 00 (disabled) / 01 (PRG terminal) / 02 (Always) 00
[
= Allowed × = Not parmitted]
Function List
If a desired parameter is not displayed, check the setting of function "b037"(function code display restriction). To display all parameters, specify "00" for "b037".