Instruction Manual Inverter X200 Series

Signal Ratings
Detailed ratings are in “Control Logic Signal Specifications” on page 4-6.
Signal / Contact Ratings
Built-in power for inputs 24VDC, 30mA maximum
Discrete logic inputs 27VDC maximum
Discrete logic outputs 50mA maximum ON state current, 27 VDC maximum OFF state voltage
Analog output 0 to 10VDC, 1mA
Analog input, current 4 to 19.6 mA range, 20mA nominal
Analog input, voltage
0 to 9.8 VDC range, 10VDC nominal, input impedance 10k
+10V analog reference 10VDC nominal, 10mA maximum
Alarm relay contacts 250 VAC, 2.5A (R load) max., 0.2A (I load, P.F.=0.4) max.
100 VAC, 10mA min
30 VDC, 3.0A (R load) max., 0.7A (I load, P.F.=0.4) max.)
5 VDC, 100mA min.
1
11
Getting started