1. INTRODUCTION
1.1 Product Description. The Predator floodlights have been
designed and tested in accordance with UL1572. These floodlights
are suitable for use in wet locations.
- The floodlight model size is referred in Figure 1.
- Major components of the floodlight are identified in Figure 1.
- The Predator floodlights have been designed to allow permanent
installation of the yoke or knuckle fitter or box mount and housing
while still providing easy maintenance and repair.
- The lamp, all electrical components, and the reflector can be
accessed by opening the door.
- Using a socket wrench, the door can be opened by loosening
captive door screws.
- All electrical components and the lens are contained on the door
and the door can be removed easily and without tools (once the
captive door screws are loosened).
®
Predator
Medium Floodlight
Wet Location
- Doors can be replaced as units and repaired in a shop under
protected conditions.
-The reflector located within the housing can be replaced as
needed. Different types of reflectors will provide different light
distributions.
1.2 Alternate Information Sources. If additional
questions arise relative to the Predator floodlight that this document
or your supplier cannot answer please refer them to:
Holophane, Field Service Department
P.O. Box 3004
Newark, OH 43058-3004
866-759-1577
2. INSTALLATION
2.1 Tools and Materials Required. The following tools
and materials are required during installation of the Predator
floodlight:
Table 1. Installation Tools and Materials
DESCRIPTION USE
3/8" hex head socket wrench Captive door screws
3/4" hex head wrench Yoke bolt
1/2" hex head wrench Box Mount
9/16 hex head socket wrench Knuckle fitter bolt and set screw
Pliers Cord grip (if applicable)
Torque wrench Captive door screws, set
(inch and foot lbs) screws and bolts
Wire nuts
2.2 Yoke Mount Installation.
2.2.1 Bolt the yoke to the mounting structure using either two 3/8"
bolts or one 1/2" grade 5 bolt. Tighten bolts securely (30-35 ft. lbs.
for 3/8" bolts or 50-60 ft. lbs. for 1/2" bolt). These bolts are not
provided.
2.2.2 Loosen the captive door screws attaching the door to the
housing. Open the door. See Figure 1.
2.2.3 Detach the power disconnect plug from the disconnect
receptacle in the housing.
2.2.4 If needed, remove the door by removing the cotter pin from
the hinge pin and sliding the door hinge pins out of the housing.
NOTE POWER CORD FITTING
The threaded hole in the back of the housing is tapped for 1/2-14
NPT.
2.2.5 Use UL approved watertight power cord fittings (not
provided) on all installations where fittings are required.
2.2.6 Remove clear protective cover and install watertight fitting.
Tighten securely.
2.2.7 Make all wiring connections in accordance with approved
wiring methods. Ensure that all supply wires and supply wire
connections are retained between the folds of the wire shield in the
housing.
2.2.8 If the door was removed as in 2.2.4 reinstalll the door by
sliding the door hinge pins into the housing. Insert the cotter pin
through the hinge pin.
WARNING-READ THESE INSTRUCTIONS
CAREFULLY BEFORE ATTEMPTING TO INSTALL OR
MAINTAIN THIS FIXTURE. WORK MUST BE DONE
BY QUALIFIED PERSONNEL.
WARNING-BE CERTAIN THAT ALL ELECTRICAL
POWER IS DISCONNECTED FROM THE FIXTURE
BEFORE INSTALLING OR MAINTAINING THE FIXTURE.
WARNING-FOLLOW LAMP MANUFACTURER'S
OPERATING AND MAINTENANCE INSTRUCTIONS.
IMPORTANT SAFETY INSTRUCTIONS
FAILURE TO FOLLOW THESE WARNINGS MAY
RESULT IN DEATH, INJURY OR SIGNIFICANT
PROPERTY DAMAGE.
DISCONTINUED

Summary of content (5 pages)