FIRElink-25 Air Sampling System INSTALLATION MANUAL
Page 2 of 40 FIRElink-25 – Installation Manual This manual details the installation of: FIRElink-25 Air Sampling System If you have any queries regarding these products or their functionality please contact: Hochiki Europe (UK) Limited Grosvenor Road Gillingham Business Park Gillingham Kent ME8 0SA Tel: +44 (0) 1634 260133 Fax: +44 (0) 1634 260132 Web: http://www.hochikieurope.com Email: psupport@hochikieurope.com ©2010 Hochiki Europe (UK) Ltd. All rights reserved.
FIRElink-25 – Installation Manual Page 3 of 40 Table of Contents 1 Introduction.................................................................................................................................... 5 1.1 Indicators ............................................................................................................................... 6 1.2 Inside the Detector ................................................................................................................. 7 1.
Page 4 of 40 FIRElink-25 – Installation Manual Mechanical Installation......................................................................................................25 4.1.1 4.1.2 Electrical Installation .........................................................................................................25 4.1.3 Power Supply Connections ...............................................................................................25 4.1.4 Signal Connections .....................................
FIRElink-25 – Installation Manual 1 Page 5 of 40 Introduction FIRElink-25 is a highly sophisticated ‘next generation‘ of High Sensitivity Aspirating Smoke Detection product that has been designed to ensure that installation and commissioning is as simple as possible, while optimising performance.
Page 6 of 40 FIRElink-25 – Installation Manual This symbol appears on the main board of the unit and indicates that the board contains static sensitive components. Suitable anti-static precautions must be taken when handling the board. Hochiki Europe (UK) Limited has taken every care to ensure that FIRElink-25 is as simple to install as possible but in case of difficulty, please contact our Product Support Department to ensure trouble free installation and operation.
FIRElink-25 – Installation Manual Page 7 of 40 1.2 Inside the Detector Removable terminal blocks (see section 1.3) Filter (see section 8) Addressable programmable interface card (FIRElink-APIC) port (see section 5.3) Detector address DIP switch (see section 5.1) RS232 serial port (see section 5.
Page 8 of 40 FIRElink-25 – Installation Manual 1.3 Detector Terminal Block Connections Normally closed FAULT relay contacts Normally open FIRE relay contacts © 2010 Hochiki Europe (UK) Ltd FIRElink-APIC addressable bus connections for use in conjunction with interface card (see sections 4.1.4 and 5.3) 9-5-0-344/ISS4/OCT10 RS485 / SenseNET connections (see sections 4.1.4and 5.2) Power supply connections (see section 4.1.
FIRElink-25 – Installation Manual 2 Page 9 of 40 Programming the Detector The FIRElink-25 may be programmed from a PC when connected to the detector via a standard 9-pin serial lead connected to the serial port of the computer and the 9 way socket at the base of the detector (see section 7.4, ‘Connecting to a PC’). In order to do this, it is necessary to install the remote control software onto the computer. A copy of the remote control software is contained on a CD-ROM supplied with each detector.
Page 10 of 40 FIRElink-25 – Installation Manual 2.2 Alarm Levels and Delays Tab 2.2.1 Alarm Levels - (Level subgroup) The value set in the Fire, Pre-Alarm and Aux functions in the Level subgroup is the relatively scaled bargraph level at which the appropriate alarm is initiated on the detector. The Fire 2 level assigns an absolutely scaled alarm level in % obs/m. The Aux level is set by factory default at level 10 which means that this alarm will occur after the Fire alarm.
FIRElink-25 – Installation Manual 2.2.5 Page 11 of 40 LDD Enable When this function is ticked, Laser Dust Discrimination (LDD™) increases the response time of the detector slightly, whilst greatly reducing the likelihood of nuisance alarms due to dust ingress. LDD may be disabled in very clean rooms for a slightly faster response to smoke by setting this function to unticking the box. This function is enabled by default.
Page 12 of 40 FIRElink-25 – Installation Manual 2.3 Day/Night Switching Tab 2.3.1 Day Start / Night Start – These values are the times to the nearest hour at which the day/night switching is desired to take place on the detector. Entries are made in 24-hour format, e.g. 19 for 7pm. Day and night switching is intended so that the detector may automatically select a different sensitivity when the protected area is unoccupied and fewer contaminants are being produced.
FIRElink-25 – Installation Manual Page 13 of 40 2.5 Device Information Tab 2.5.1 Device Type This function is for display purposes only. It shows any special designation for the unit, which will normally be FIRElink-25. 2.5.2 Firmware Version This function is for display purposes only. It shows the version number of the fitted firmware chip. 2.5.3 Run-time Hours This function is for display purposes only.
Page 14 of 40 FIRElink-25 – Installation Manual 2.7 Flow Monitoring Tab 2.7.1 Flow Rate This function is for display purposes only, and shows a value corresponding to the current airflow through the detector. 2.7.2 Flow High Limit This value is the level above which airflow needs to increase to trigger a fault indication (which may indicate a loose or damaged inlet pipe). Flow low limit and Flow high limit parameters are automatically set up on initial power-up. 2.7.
FIRElink-25 – Installation Manual 2.8.2 Page 15 of 40 Chart Recording Rate This function controls how frequently the detector and alarm level or flow rates are stored in the FIRElink25’s internal chart recorder log. (See section 2.10, ‘Chart Recording’).
Page 16 of 40 FIRElink-25 – Installation Manual to allow for a scheduled maintenance period. The detector will then generate a separator fault at the planned time regardless of the condition of the separator, although degradation of the separator to below 80% efficiency before this date will override this. See section 8, “Maintenance” for further details. 2.8.
FIRElink-25 – Installation Manual Page 17 of 40 Smoke Density histogram Alarm flags There are two types of smoke density histogram; one shown in blue (the “fast” histogram) which updates every 15 minutes, feeding information to the long-term “slow” histograms (which appear in yellow). These set the detector sensitivity based on the ambient smoke conditions and it takes 24 hours for the two slow histograms (the “day” and the “night” histograms) to complete their learning phase (see section 2.2.6).
Page 18 of 40 FIRElink-25 – Installation Manual 2.10 Chart Recording The chart recording function shows how smoke density in the protected area has varied over time. The chart may be downloaded to disk or printed out from a connected printer. To access the chart log, select the menu options View > Chart Recording or click the button on the toolbar as indicated below: The following screen is displayed: The red trace is the current alarm level and the black trace is the detector output.
FIRElink-25 – Installation Manual Page 19 of 40 A list will appear of all detector settings files stored on the current drive. As a special case, if desiring to recall the factory default settings, there is a file named ‘default.dfs’ in the ‘remote2k’ directory. Loading this file will reset the detector to the factory default.
Page 20 of 40 3 FIRElink-25 – Installation Manual Design Limitations FIRElink-25 is intended to provide LOCALISED incipient fire detection only. This means that it is suitable for the substantial range of applications typified by; small non-compartmentalised rooms, warehouse racking, or pieces of electronic or electromechanical equipment where it is desirable to achieve individual incipient fire reporting. In compartmentalised rooms, each compartment would normally use individual FIRElink-25 detectors.
FIRElink-25 – Installation Manual Page 21 of 40 B Above Ceiling Sampling with detector mounted in ceiling void. 3.1 System Design Simple designs with short sampling pipes produce the best results. Complex sampling pipe runs should be avoided with the FIRElink-25 detector. The use of ‘T’ branch-pipes is not recommended. To assist in design and to verify system performance, it is advisable to use the FIRElink PipeCAD® sampling pipe modelling software.
Page 22 of 40 FIRElink-25 – Installation Manual 3.2 EN54-20 Compliance The installation must be designed using PipeCAD software, which is provided free on the CD shipped with each detector. After designing the installation including pipes, endcaps and sampling holes, enter the detector type in the “Type” drop-down list in “Options” “Calculation options”. Select “Options” “Calculate” or click on the calculator icon.
FIRElink-25 – Installation Manual Page 23 of 40 compliant. If functions are changed, it is recommended that the system is retested if continuing compliance is in any doubt. *The results should be verified at installation by entering the installed detector's Fire 1 sensitivity (as indicated in the remote software histogram screen) into the PipeCAD “Options/Calculation options/Detector sensitivity” field and recalculating the layout results.
Page 24 of 40 4 FIRElink-25 – Installation Manual Installation Before installing the detector the local standards for installation of aspirating detection systems must be consulted as these standards differ throughout the world. Specific advice for one country may not be applicable to another. The following is a brief set of guidelines on installing detectors: The detector will normally be mounted at a level where there is easy access to the unit for configuration and programming.
FIRElink-25 – Installation Manual Page 25 of 40 Piped Exhaust Docking Station 4.1.1 Mechanical Installation The docking station is connected to the installed sampling pipe-work and fixed to the wall or mounting surface using 3 off screws of a type appropriate to the mounting surface. Ensure that the sampling and/or exhaust pipes are securely seated in the pipe ports before fixing.
Page 26 of 40 FIRElink-25 – Installation Manual The following illustration shows the power and signal connections to the docking station for connection to a single SenseNET cable: Power Supply Screen Wire to Earth Stud SenseNET/RS485 Bus A Wire SenseNET/RS485 Bus B Wire SenseNET/RS485 Bus Screen Wire Power Supply 0V Wire Wire from "Earth" Terminal to Earth Stud Power Supply +24V Wire 4.
FIRElink-25 – Installation Manual Page 27 of 40 Dock Fixing Screws Cover Fixing Screws Cover Fixing Screws © 2010 Hochiki Europe (UK) Ltd 9-5-0-344/ISS4/OCT10
Page 28 of 40 5 FIRElink-25 – Installation Manual Interfacing Because of the flexible nature of the FIRElink-25 detector and the many possible configurations, there are many options for interfacing the detectors to the Fire Panel. These include many third party interfaces available from various manufacturers. Because of this, it is not possible to give a complete list of all interfacing methods but the following pages will give details of the most common methods that are likely to be used. 5.
FIRElink-25 – Installation Manual Page 29 of 40 5.2 Connecting a FIRElink-25 to a SenseNET/RS485 Detector Network Up to 127 detectors may be linked in a single SenseNET bus, supporting a total length of wire between adjacent detectors of up to 1.2km. In the above example, two FIRElink-25 detectors are linked into a 127-detector bus with a Command Module and a number of other FIRElink detectors.
Page 30 of 40 FIRElink-25 – Installation Manual FIRElink-APIC Mounting Studs FIRElink-APIC Address Switches (x 2) FIRElink-APIC Interface Connection The connections to the Fire Panel are made using the BUS L1 and H1 (bus 1 input and output) and the BUS L2 and H2 (bus 1 input and output) terminal connectors shown in Section 4.1.4. The only settings that need to be made are on the FIRElink-APIC address DIP switches. The start loop address Is entered on SW1 and the end loop address on SW2.
FIRElink-25 – Installation Manual Page 31 of 40 5.4 Connecting to a PC To connect a single stand-alone detector to a PC, connect the PC‘s serial port directly to the detector‘s 9way RS232 port, which is situated on the bottom surface of the detector case.
Page 32 of 40 6 FIRElink-25 – Installation Manual Event Log An event is defined as a change to any programmed function a signal received from an external controller such as the remote software, FIRElink-APIC or SenseNET a detector output level meeting or exceeding the Pre-Alarm, Aux, Fire 1 or Fire 2 alarm thresholds a fault condition such as a flow or separator fault start of day / night operation demonstration mode start / stop FastLearn start / stop Power on or off The
FIRElink-25 – Installation Manual Page 33 of 40 Open: opens a previously saved event log. Event logs have the file extension “.evl”. Save As: saves the current event log as a .evl file with a user defined name. Print: prints the event log to a connected printer. Filter: clicking on this option displays the following screen: This allows the user to limit the information printed or viewed on the PC screen. For example the user might wish to concentrate on alarm events only.
Page 34 of 40 7 FIRElink-25 – Installation Manual Commissioning Before commissioning the detector the local standards of aspirating detection systems must be consulted. These standards differ widely throughout the world and specific advice for the market in one country may not be applicable to another. Commissioning strategy will initially depend upon the environment in which the detector is installed.
FIRElink-25 – Installation Manual 8 Page 35 of 40 Maintenance FIRElink-25 is a very low maintenance detection system. If required, external cleaning of the unit should be performed using a damp (not wet) cloth. Do not use solvents as these may mar the front panel label. The only part that may require field replacement during servicing is the dust separator assembly.
Page 36 of 40 FIRElink-25 – Installation Manual Click on the list entry to highlight it and click on the Diagnostics button. The software will then commence the system tests. During the “Aspirator and flow” test, the detector fan will suddenly slow down, but this is a normal part of the test.
FIRElink-25 – Installation Manual 9 Page 37 of 40 Troubleshooting 9.1 Nuisance Alarms Occur Too Often Check that the ClassiFire alarm factor setting is appropriate for the normal working environment of the protected area. See section 2.2.4 Check that the detector is not in Demonstration mode. This can be ascertained by viewing the event log (see section 2) and checking that the entry Demo mode has a higher log entry number than the most recent FastLearn start and FastLearn end entries.
Page 38 of 40 FIRElink-25 – Installation Manual protected area to ensure normal flow. This will require the detector to be installed using the piped exhaust docking station (see section 4.1). 9.5.1 "Low Flow" Error Messages. Check that the pipe giving the error is not blocked Check that the low flow fault threshold is not set too high (see section 2.7.3) 9.5.
FIRElink-25 – Installation Manual Page 39 of 40 10 Do's and Don'ts DO Ensure that the ClassiFire alarm factor is appropriately set. Ensure that cables are correctly connected before powering up by use of cable identifiers or electrical continuity checks. Incorrect connection could damage the detector. Ensure that cable of an appropriate approved type is used for interconnection. Place sampling points so that the detector will be able to detect smoke at the earliest opportunity.
Page 40 of 40 FIRElink-25 – Installation Manual 11 FIRElink-25 Specification SELV Rating (EN 60950) Supply Voltage Size (mm) Weight Operating Temperature Range Operating Humidity Range Measurement Range (obs/m) Detection Principle Particle Sensitivity Range Current Consumption Relay Contact Rating Maximum Sampling Pipe Length Sampling Pipe Inlets Sampling Pipe Internal Diameter Alarm levels Chamber Service Intervals Dust Separator Replacement Intervals Laser Lifetime (MTTF) Programming Data Bus Cable D