2.8.2 Chart Recording Rate
This functi on controls how frequentl y the det ec tor and al arm l ev el or flow r ates are stor ed in the FIRElink-
25’s int er nal chart recor der log. (See section 2.10, ‘Char t Recordi ng’).
0 Detec tor Output 1 second 10 seconds
1
De te ctor Outp u t
5 seconds 50 seconds
2
De te ctor Outp u t
12 seconds 2 minutes
3
De te ctor Outp u t
30 seconds 5 minutes
4
De te ctor Outp u t
1 minute 10 minutes
5
De te ctor Outp u t
2 minutes 20 minutes
6
De te ctor Outp u t
5 minutes 50 minutes
7
De te ctor Outp u t
10 minutes 100 minutes
8
De te ctor Outp u t
20 minutes 200 minutes
9
De te ctor Outp u t
50 minutes 500 minutes
10 Flow Recording 1 second 10 seconds
11
Flow Recording
5 seconds 50 seconds
12
Flow Recording
12 seconds 2 minutes
13
Flow Recording
30 seconds 5 minutes
14
Flow Recording
1 minute 10 minutes
15
Flow Recording
2 minutes 20 minutes
16
Flow Recording
5 minutes 50 minutes
17
Flow Recording
10 minutes 100 minutes
18
Flow Recording
20 minutes 200 minutes
19
Flow Recording
50 minutes 500 minutes
In the above table the shaded cells indic ate flow rat e r ecording whil st the white cell s indi c ate detector and
alarm leve l recording.
At the slowest rec or ding rat e, one month of data can be recor ded. The factory default setting is 8.
2.8.3 Separator Condition
The v alue given at this func tion is the efficiency rating of t he dust separat or element in the detector as a
percentage of the eff ic iency of a cl ean separat or . A new element will give a r eading of 99 in this function.
When the eff ic iency has decreased to 80%, t he Fault indic ator LED will illum inate and the event log will
show “Separat or r enew”.
NOTE: Fit ting a new element will r eset this figure to 99
2.8.4 Separator Change Date
This function def aults to “--“, which means that a separator fault will onl y appear when the eff iciency
decrease s to 80% ( see 2.8.3, “Separator Condit ion”). However, a date may be enter ed i nto this function
Setting Type Storage Interval Time pe r Div ision on C ha r t Log