prot ec ted area to ensure normal flow. This will r equir e the det ec tor to be inst alled using the piped
ex haust doc k ing station ( see section 4.1).
9.5.1 "Low Flow" Error Messages.
Check that the pipe giv ing the error is not blocked
Check that the l ow flow fault t hr eshol d is not set too high (see secti on 2.7.3)
9.5.2 "High Flow" Error Messages
Check that the pipe is pushed home into the inlet and is not brok en or c r ac k ed
Check that install ed pipe-work i s fitt ed with an end-cap. The FIRElink Pi peCA D® pipe modelling
sof twar e pr ompt s the use of appr opri ate end-caps.
Open bore pipes are not recommended.
Check that the high flow fault threshold i s not set too low (see sect ion 2.7. 2)