9.4  Connecting a Single FIRElink-400 to an Addressable Fire 
Panel 
An FIRElink-APIC may be used to decode detector status information and relay this to the Fire Panel via 
the Addressable Bus 1 and Bus 2 terminal block connections (see section 185619544.01.1.1 ”Detector 
Terminal Block Connections” on page 33). 
NOTE: The detector 
address on the 
RS485 
communications loop 
and the Fire Panel 
addressable protocol 
address are the 
same, in other 
words, no address 
translation is 
performed. 
9.5  Connecting to a PC 
To connect a single stand-alone detector to a PC, connect the PC‘s serial port directly to the detector‘s 9-
way RS232 port. Connections for this cable are shown below: 