8 Configuration 
Configuration is carried out via the DIL switch mounted on the Main PCB. 
Switch 
1 
Switch 
2 
Switch 
3 
Switch 
4 
Switch 
5 
Switch 
6 
Switch 
7 
Switch 
8 
Set Detector 
Sensitivity 
Alarm Factor 6 
Off Off 
Alarm Factor 7  On  Off             
Alarm Factor 8  Off  On             
Alarm Factor 9  On  On             
ClassiFire
®
 Enabled 
Off 
Fixed Alarms 
Enabled 
    On           
Flow Limit Offset 
±40        Off  Off       
±20        On  Off       
±5       
Off On 
±3        On  On       
Flow Delay 
240sec           
Off 
30sec            On     
Input Select 
PSU Fault             
Off 
ClassiFire Override              On   
Auto Calibration 
Enable               
Off 
Disable                On 
NOTE: Text in red denotes the EN 54-20 test configuration (factory default) setting. 
8.1 Alarm Factor 
The detector calculates sensitivity relative to the ambient environmental conditions. Higher Alarm Factors 
provide reduced sensitivity (the Alarm threshold is maintained further away from the ambient level). Refer 
to the Remote Software manual for further details. 
NOTE: Changing the Alarm Factor starts a new FastLearn cycle: during the initial 15 minute learning 
period, the detector is incapable of reporting an alarm. The unit will take 24 hours to achieve 
optimum performance, based on the ambient conditions. 
8.2 ClassiFire
®
 Enabled 
Allows the artificial intelligence system to continuously adjust Alarm thresholds in order to avoid unwanted 
Alarms from environmental changes (recommended). 
NOTE: Enabling this feature means that nuisance alarms due to fluctuations in the ambient environment 
become less likely. 