8.3 Fixed Alarms Enabled 
Switches the artificial intelligence system off, locking sensitivity to that set at initial setup. This de-
activates the dust filter monitoring system (not recommended). 
NOTE: Enabling this feature means that nuisance alarms due to fluctuations in ambient pollution levels 
become more likely. 
8.4 Flow Limit Offset 
Sets the sensitivity of the airflow monitoring system.  A small offset makes the system very sensitive to air 
flow changes. EN 54-20 systems must react to a ±20% change in airflow, which equates to a change in 
flow sensor output of +
5 (this refers to a percentage of flow sensor full output and is not a direct measure 
of airflow). Areas with fluctuating air pressures may require a less sensitive setting. 
NOTE: Changing the flow limit offset starts a new flow calibration set up. 
8.5 Flow Delay 
Sets the period during which abnormally high or low air flow conditions must continue before the unit 
indicates a “Flow” fault. 
8.6 Input Select 
When this switch is set to the factory default OFF position, the detector input terminals may be connected 
to a power supply fault output relay so as to generate a detector “Fault” condition if the power supply 
Fault relay contacts open. If power supply monitoring is not required, either a wire link can be placed 
across the input terminals, or this switch can be set to ON to remove the fault. 
Setting the switch to ON enables the ClassiFire
®
 Override feature. This reduces detector sensitivity by 
50% as long as there is a short circuit across the input terminals, e.g. controlled by a key switch. This can 
be used to prevent unwanted Alarms during planned intervals of smoke release, e.g., incense burning 
during a church service.  
NOTE: If a wire link is fitted across the INPUT terminals, it is important that this switch be set to OFF, or 
the detector sensitivity will be dramatically reduced by the ClassiFire
®
 Override function being 
permanently enabled. 
8.7 Auto Calibration 
Automatically starts a new FastLearn cycle when the detector is powered up. This may be disabled if the 
previous settings need to be retained. 
NOTE: if this function is enabled, the unit will also recalibrate the flow sensors after power up. 