1.4  Long Transport Times: 
The sampling pipe may be too long, may have too many sampling holes/capillaries, or may have 
incorrectly sized holes. 
Check design with pipe modelling software. 
Sampling pipes, sampling holes and/or the exhaust pipe may be partially blocked by dust or debris. 
Clean pipework with dry compressed air and/or clean the sampling holes. 
Fan may be defective. 
Send detector for repair. 
Fan lead may be disconnected 
Reconnect lead. 