12  Optional Communications Card 
A communications card may be fitted inside the detector. 
Board Locating Post 
Detector Address DIL Switch 
The detector address is set using a reverse binary code, i.e. switch 1 is the least significant bit 
and switch 7 is the most significant bit. Switch 8 is not used. 
Set the address from 001 to 127 in order to identify the detector. Addresses in a detector 
network do not have to be consecutive but must be different. 
2 off M3 x 6 Fixing Screws 
Provided with board. 
RS-232 Serial Port 
Use 9-pin D-type null modem cable to connect to PC. 