13 Technical Data 
NOTE: Some devices such as sounders and beacons have high inrush currents on activation, which can 
damage relay contacts. It is good practice to consider fitting a suitable current limiting resistor in 
series with the load to avoid this potential problem. 
SELV Rating  EN 60950 Class III 
Supply Voltage.  21.6v – 26.4v DC 
Current Consumption  350mA 
Electrical Safety  Complies with EN 610190-1 
Size (mm)  190w x 230h x 110d 
Weight 1.2kg 
Operating Temperature Range. 
0°C to 38°C (UL 268) 
-10°C to 60°C (EN 54-20) 
Operating Humidity Range 
0 to 90% relative humidity, non-condensing 
EN61010-1 Pollution Degree 1 
EN61010-1 Installation Category II 
IP Rating  IP50 
Sensitivity Range  0.4% to 25% obscuration/metre 
Detection Principle  Laser light forward scattering mass detection 
Maximum Number of Sampling 
Holes 
Class A: 2 
Class B: 4 
Class C: 10 
Maximum Sampling Pipe 
Length 
50m 
Sampling Pipe Inlets  2 off 3/4” pipe inlets (sampling pipe and exhaust) 
Alarm / Fault Relays  Pre Alarm / Fire / Fault 
Relay Contact Rating 
(Changeover) 
1A at 24V DC (resistive load) 
Programming  Internal DIL switches 
PC Interrogation.  Via optional Communications Card 
APIC Compatible  Yes 