Submittal Sheet

110
P
UMPS
Pumps
Boiler Feed Units (Stock, continued)
Discharge Pump
Pressure Capacity Motor Receiver
Model Part Sq. Ft. Boiler Total Storage Storage
Number Number EDR Pumps HP (kW) PSIG (kPa) GPM (LPS) HP (kW) Gal (Liters) Gal (Liters) Minutes
30VBFS-B 161024 4,200 Simplex 30 (22) 20 (138) 9 (0.6) 1/3 (0.2) 30 (114) 18 (68) 9
30VBFD-B 161025 Duplex
50VBFS-B 161001 7,000 Simplex 50 (37) 20 (138) 15 (0.9) 1/3 (0.2) 50 (189) 39 (148) 11
50VBFD-B 161002 Duplex
100BFS-B 161003 13,800 Simplex 100 (75) 20 (138) 15 (0.9) 1/3 (0.2) 100 (379) 83 (314) 11
100VBFD-B 161004 Duplex
200VBFS-20 161026 27,800 Simplex 200 (149) 20 (138) 30 (1.9) 1/2 (0.4) 200 (757) 172 (651) 12
200VBFD-20 161027 Duplex
200VBFS-30 161006 27,800 Simplex 200 (149) 30 (207) 30 (1.9) 1 (0.7) 200 (757) 172 (651) 12
200VBFD-30 161007 Duplex
Ordering Information
Open drip proof motors only. Single phase, 60Hz, 115/230 volt.
For systems up to 27,800 sq. ft. EDR or up to
200 (149 kW) Boiler HP
Vertical steel receiver with mounting feet
Available with pumps in simplex or duplex design
Low height NPT inlet for easy return line piping
Separate NPT connections provide a secondary vent
for safe operation
NPT drain connection
Float operated internal water make-up water feeder
100% factory tested as a complete unit
Includes water level gauge with protective brass rods
and shut-off valves
Optional equipment
Inlet basket strainer
Y-strainer
Control panels for wall mounting
Pump seal maximum temperature 250˚F (121°C)
Pump maximum temperature
207˚F (97°C) Model 200VBFS-30 & 200VBFD-30
210˚F (99°C) All other Models
Series VBF
®
Series VBF Simplex Design
Series VBF Duplex Design

Summary of content (2 pages)