Instruction Manual

Installation and
Maintenance
Manual
1. INTRODUCTION
1.1 Product Description. The Predator floodlights have been
designed and tested in accordance with UL844 and UL595. These
floodlights comply with applicable paragraphs of Sections 501, 502,
and 503 of the National Electrical Code.
-The fixture identification label provides information regarding
suitable environmental applications.
-The floodlight model size is referred to in Figure 1.
-Major components of the floodlight are identified in Figure 1.
-The Predator floodlights have been designed to allow permanent
installation of the yoke or box mount and housing while still
providing easy maintenance and repair.
-The lamp, all electrical components, and the reflector can be
accessed by opening the door.
-Using a socket wrench, the door can be opened by loosening
captive door screws.
AFTER INSTALLATION DELIVER THIS
MANUAL TO OWNER
GR421
IM-60-C
Predator
®
Small Floodlight Marine
-All electrical components and the lens are contained on the door
and the door can be removed easily and without tools (once the
captive door screws are loosened).
-Doors can be replaced as units and repaired in a shop under
protected conditions.
-The reflector located within the housing can be replaced as
needed. Different types of reflectors will provide different light
distributions.
1.2 Alternate Information Sources. If additional
questions arise relative to the Predator floodlight that this document
or your supplier cannot answer please refer them to:
Holophane
Field Service Department
P.O. Box 3004
Newark, OH 43058-3004
866-759-1577
2. INSTALLATION
2.1 Tools and Materials Required. The following tools
and materials are required during installation of the Predator
floodlight.
TABLE 1. Installation Tools and Materials
DESCRIPTION USE
3/8" hex head socket wrench Captive door screws
3/4" hex head wrench Yoke bolt
1/2" hex head socket wrench Box Mount
Pliers Cord grip (if applicable)
Torque wrench Captive door screws and bolts
(inch and foot lbs.)
Wire nuts
2.2 Yoke Mount Installation.
WARNING
DO NOT USE A PHOTOCONTROL IN A LOCATION
HAVING A UL CLASSIFICATION OF CLASS I, DIV. 2
OR CLASS II, DIV. 1. DO NOT USE FUSING IN A
LOCATION HAVING A UL CLASSIFICATION OF
CLASS I. FAILURE TO FOLLOW THESE WARNING
INSTRUCTIONS MAY RESULT IN FIRE AND
SIGNIFICANT PROPERTY DAMAGE.
2.2.1 Bolt the yoke to the mounting structure through the provided
holes in the yoke using two 3/8" bolts (not provided).
2.2.2 Loosen the captive door screws attaching the door to the
housing. Open the door.
2.2.3 Detach the power disconnect plug from the disconnect
receptacle in the housing.
2.2.4 If needed, remove the door by removing the cotter pin from
the hinge pin and sliding the door hinge pins out of the housing.
2.2.5 Use UL approved watertight power cord fittings (not
provided) on all installations. If installed in a Marine location, use
rigid metal conduit or AVC Marine cable (not provided) and water-
tight cable grip fittings (not provided) for power supply conductors.
WARNING-READ THESE INSTRUCTIONS
CAREFULLY BEFORE ATTEMPTING TO INSTALL OR
MAINTAIN THIS FIXTURE. WORK MUST BE DONE
BY QUALIFIED PERSONNEL.
WARNING-BE CERTAIN THAT ALL ELECTRICAL
POWER IS DISCONNECTED FROM THE FIXTURE
BEFORE INSTALLING OR MAINTAINING THE FIXTURE.
WARNING-FOLLOW LAMP MANUFACTURER'S
OPERATING AND MAINTENANCE INSTRUCTIONS.
IMPORTANT SAFETY INSTRUCTIONS
FAILURE TO FOLLOW THESE WARNINGS MAY
RESULT IN DEATH, INJURY OR SIGNIFICANT
PROPERTY DAMAGE.
DISCONTINUED

Summary of content (4 pages)