HOME-FLEX CSST 31
Meter connections
4.5 Meter connections
Natural gas meters are generally structurally supported independent of the building struc-
ture and piping system. When the gas meter is independently supported, HOME-FLEX® can,
in some localities, be used to connect the meter to the building gas system. If the gas meter
is not supported independent of the building structure or gas piping system, HOME-FLEX®
tubing cannot be used to connect directly to the meter.
Connection by Special Termination Fitting
Do not use HOME-FLEX® CSST as a direct connection if the meter must be supported by the
piping system. If the meter is supported by the building structure, common practice is to
route the CSST system to a termination ange mounted to the exterior of the building, and
to connect the meter to the termination ange with rigid pipe. Alternatively, rigid pipe can
be used to penetrate the building, with an attachment to HOME-FLEX® inside the structure.
(Figure 4.14)
Direct Connection
If a direct connection from HOME-FLEX® to an independently supported gas meter is per-
mitted by the local utility, the connection should include an extra 3-6" of length to allow for
building settling and meter movement. Exposed sections of CSST are to be wrapped with
self-bonding silicone tape, especially if the building is of masonry construction. For direct
connections through masonry construction, a PVC sleeve is required, and also recommended
for wood frame construction. (Figure 4.15)
Figure 4.14 Connection to Building supported Meter
Sleeve
(if required)
Sealant
(typical)
Termination
Fitting
Service Line
Meter
House Service
Regulator
Note: Diameter of hole shall
be at least 1/2" greater
than OD of tubing and shall
be sleeved in accordance
with local building code (if
applicable).
Figure 4.15 Independently Supported Meter
Sealing
Radius of 3-6"
Note: Check with the local servicing utility prior to directly connecting HOME-FLEX® to the
gas meter as utilities regulate connections to meter attachments.
4.6 Appliance connections
Termination Fittings with Appli-
ance Connectors
The HOME-FLEX® termination
ange tting is designed to ser-
vice moveable appliances and
quick-connect devices at oor
and hallow wall piping outlets
(Figure 4.16) in combination with
a HOME-FLEX® Flexible Appliance
Connector or similar approved
device. The termination outlet
Figure 4.16 HOME-FLEX® Connection to Movable Gas Appliance
Moveable
Appliance
Shut-off
Valve
Termination
Fitting
Flexible Protec-
tive Conduit
Mounting
Brace
HOME-FLEX
®
Appliance
Connector