Installation Guide

18
Sizing and Congurations
400 CFH, which at 70 feet can be supplied by 1¼" pipe with a maximum capacity
of 490 CFH. 1¼" pipe is the correct size for section A2.
To size section A3, we can reduce the load by another 190 CFH to 210 CFH for the
remaining heater and the water heater. At 70-feet, 1" pipe can supply a maximum
of 240 CFH, which is sucient for the run. 1" pipe is the correct size.
To size section A4, the load is reduced to just the 60 CFH of the water heater. At
70-feet, ½" pipe can provide a maximum capacity of 61 CFH. ½" pipe is the correct
size for section A4.
Step 2 Size Section E: The length is the length of the black pipe plus the length of the
HOME-FLEX® run = 70 feet, and total load is 60 CFH. Referencing Table 7.1, ¾" tubing provides
a maximum capacity of 76 CFH at 70 feet. ¾" Tubing is the correct size for section E.
Step 3 Size Section D: The length is the length of the black pipe up to the branch and the
length of the HOME-FLEX® run = A1 + A2 + A3 + D = 60 feet. Load is the load of the heater,
150 CFH. At 60 feet, 1" inch CSST can provide a maximum capacity of 156 CFH. 1" is the correct
size.
Step 4 Size Section C: The length is 40 feet and total load is 190 CFH. At 40 feet, 1" tubing
provides a maximum of 195 CFH. 1" Tubing is the correct size.
Step 5 Size Section B: The length is 20 feet and total load is 200 CFH. At 20 feet, 1" tubing is
required to provide at least 200 CFH, with a maximum capacity of 288 CFH.