Installation Guide

13
Sizing Methods and Examples
Step 3 Determine the number and type of HOME-FLEX Underground® ttings that are
required in the system. Add the equivalent number of feet from Table 5.1 “Length to Add to
Each Run for Each Fitting” on page 21 of this guide to the number of feet calculated above.
Step 4 Use Table 5.7 on page 27 for 10 PSI elevated pressure LP Gas. Find the nearest length
that is equal to or greater than the length calculated in step 3 above. Follow the row across
until the number of BTU’s provided is equal to or greater than the required BTU’s required for
this run - check the column header for required pipe diameter.