Hazard information
Exceeding this capacity could lead to the
destruction of the device, fires or electric shocks.
The circuit to the which the device and the load
will be connected has to be secured by a cable
protection switch in accordance with EN60898-1
(tripping characteristic B or C, max. 16 A rated
current, min. 6 kA interrupting rating, energy
limiting class 3). Installation regulations according
to VDE 0100 and HD382 or 60364 have to be
considered. Users must be able to easily access
the cable protection switch. This must be marked
as disconnecting device for the actuator.
Before the actuator is connected, remove the
fuse from the fuse box
.
The device has not been designed to support
safety disconnection.
Devices with electronic power supply units (e.g.
TV or high voltage LED light sources) are no
ohmic loads. They can generate inrush currents
with more than 100 A. Switching such kind of
loads may lead to premature wear of the actuator.
In such cases, we recommend to use switch-on
current limiters at the switching outputs.