Cisco Edge 300 Series Switch Installation Guide
OL-24909-01
Installing the Switch
Installing the Switch in a Cabinet
You can install the switch in a ventilated cabinet. To ensure adequate ventilation, make sure that the
cabinet meets the following specifications:
Minimum dimensions (H x W x D): 19.69 x 19.69 x 15.75 inches (50 x 50 x 40 cm)
Ventilation openings:
The front panel must have one ventilation opening measuring at least 11.81 x 5.91 inches
(30 x 15 cm). The ratio of the ventilation openings should be greater than 30%.
Each side panel must have two ventilation openings (one along the top, and one along the
bottom) measuring at least 12.60 x 3.54 inches (32 x 9 cm). The ratio of the ventilation openings
should be greater than 30%.
Switch placement:
For wall-mount placement, install the switch at the rear of the cabinet.
For desktop placement, place the switch at the center of the cabinet.
Figure 12 Cabinet Dimensions
1 11.81 x 5.91 inches (30 x 15 cm) 4 19.69 inches (50 cm)
2 12.60 x 3.54 inches (32 x 9 cm) 5 19.69 inches (50 cm)
3 15.75 inches (40 cm)