How to use the receptacle
When two or more receptacles are used, refer to the table below and apply
the load to each receptacle equally to prevent overloading.
Voltage fluctuation can be prevented by applying the load equally to the
single phase receptacles.
Receotacle I 240
V
120v
\
Case
50 A
30 A
50 A
30 A 20 A
Max.
for both
usmg LLCU v only 4 I. I H Iwax., JU H Iwax.
41.7 A Total
Using both
120 V
Total 10
A
Total
63.3 A
and 240 V
Total 20
A
Total
43.3 A
Total 30
A
Total
23.3 A
When both 240 V and 120 V receptacles are use, be sure that the ampere
draw at each receptacle is less than the specified capacity and the total
ampere(s) are less that 83.4 amperes.