OPERATION
GFCI System
(120V-30A, 120V/240V-30A, 120V/240V-37.5A Receptacles)
1. Unplug all tools and appliances from the generator.
2. Start the engine (see page 29).
3. Turn the AC circuit breaker to the ON position.
4. Turn OFF the Auto Throttle switch (see page 30).
5. Press the GFCI TEST button:
The RESET button should extend, and the AC circuit breaker
should switch to the
OFF position.
If the GFCI and AC circuit breaker do not function as described, take
the generator to an
authorized Honda generator dealer for repair.