Owner's Manual

Inspection:
Always check GFCl operation before using the generator.
You risk electric shock if you operate this generator with a faulty GFCl
(ground-fault circuit interrupter).
Test GFCl before use.
If GFCl fails test,
do
not use your generator. See your Honda dealer.
1.
Unplug all tools and appliances from
the
generator.
2.
Start the engine.
3.
Turn the circuit breaker to the
ON
position.
4.
Turn the autothrottle switch to the
AUTO-THROTTLE SWITCH
/
OFF position.
5.
Press the GFCl TEST button. The
RESET button should extend, and
the circuit breaker should switch
to
the
OFF position.
OFF
If the GFCl and circuit breaker do not function as described, take the
generator
to
an authorized Honda generator dealer for repair.
GFCl TEST BUlTON CIRCUIT BREAKER
\
GFCl
RESET,BUlTON
/
\y
/
/II
AI
18