Operation Manual

6 EN
Value for an admissible voltage drop on-line of 7 V and an
admissible current of 7 A per mm
2
of cable section:
- ambient temperature: 20 °C,
- completely unwind the cable to avoid deterioration of the
insulation by over-heating,
- comply with the cable manufacturer’s instructions.
This generator is not recommended for use with electronic
apparatus, such as televisions, hi-fis, or microcomputers,
which might not be compatible with it.
Avoid overloading the generator; the following rules must be
respected if the generator is to perform properly:
- the sum of the power outputs of the machines connected
simultaneously to the generator must be compatible with
the characteristics given in the page 10 of this manual,
- some appliances draw more power when starting up than
their nominal power rating (electric motors and
compressors are examples). We recommend that you
contact a Honda dealer in case of doubt,
- do not exceed the maximum current specified for each
receptacle.
The generator must not be loaded to its nominal power if
conditions are such that the normal cooling requirements
are not met (atmospheric pressure: 100 kPa [1 bar]).
When using the generator in unfavourable conditions, take
care to reduce the power load.
Example: 28 A* (* limited to x A by the circuit breaker).
INFORMATION ON THE CONSTRUCTION OF THE
GENERATOR
The generator windings are not connected to the earth; the
system is thus safe by construction and limits the risks of
electrocution. It is strictly forbidden to connect the coils to the
generator earth, except when using a 30 mA differential circuit
breaker for the protection of persons. The installation of such a
device must be carried out by a specialist electrician and requires
all appliances to be earthed.
The differential circuit breaker acts as a check against faulty
insulation. It cuts off the power when there is a detectable fault in
the insulation between a voltage-bearing conductor and any part
of the earth, on the output side of the differential circuit breaker.
ECT7000 (230/400 V)
The three 230 V single-phase receptacles are connected in
parallel to the terminals of a winding specially reinforced to
withstand a current of 20 A. The single-phase 230 V power output
given on the rating plate, and also indicated in the table of
characteristics, is available only on these receptacles and when
no other three-phase load is connected to the generator outputs.
Never connect the generator three-phase receptacle to a
singlephase splitter box.
When using simultaneously 230 V single-phase and 400 V three-
phase current, the current intensity per phase must not exceed
10 A.
Ex: Power available from receptacles for simultaneous three-phase
and single-phase use.
This type of generator is fitted with a thermal circuit breaker which
acts as a protection against overload. If the distribution of electric
current is interrupted during use, this might be caused by an
overload tripping the thermal circuit breaker. If this happens, wait
a few moments, eliminate the cause of the overload, then reset
the circuit breaker by pressing the button [1] sited near to the AC
receptacles. The thermal circuit breaker is rated according to the
specifications of the machine; if it needs replacing, use an original
Honda component.
Three-phase
0 3000 W 4000 W 5000 W 6000 W 7000 W
Single-phase
4500 W 1300 W 950 W 650 W 300 W 0
GV-F-W
[1]
B
[2] [1]
IT
[1]
EC2000
B
[1]
[2]
GV
[1]
IT
[1]
F
[1]
EC3600
IT F
GV
ECT7000
[1]
[1]
[1]
IT
GV F
B
[1]
[2]
[1]
[1]
EC5000
[1]