Operation Manual

20
AC RECEPTACLE SELECTION
Main power circuit
Main Circuit I
Main Circuit II
Receptacles powered
by each main circuit
Power distribution
120V 30A
120V 20A
120/240V 20A
(LOCKING PLUG)
The generator has two separate main power producing circuits.
These two circuits supply equal power to different receptacles
shown when the voltage selector switch is in the 120/240V
position.
When two or more receptacles are used; prevent overloading by
dividing the load between the two power circuits.
The chart below shows the rated load in amperes that can be
connected to each receptacle to balance the generator.
The total rated ampere draw is 25.0A.
The table shows the specifications when the 120/240V locking
plug receptacle is used for 120V.
2and3
1
2 4=12.5A max.
1=12.5A max.
Example:
Receptacle 2 has a 10A load connected to it. Receptacle 3 has a 10
A load connected to it. Both receptacles are powered by main
power circuit I. The equation tells us that the total power draw on
circuit I is 20A. This is a substantial overload of this circuit. To
eliminate the excess power draw on circuit I, the load from
receptacle 2 should be switched to receptacle 1. Now circuit I is
powering the 10A load (less than 12.5A) and circuit II is powering
the 10A load (less than 12.5A).