Installation Instructions

Table Of Contents
Installation
Part No.: 4417781 Wireless Field Interface
Installation Manual 4 - 5
4.4 Install the BPM cable
The BPM signal lines enter the enclosure through a dedicated gland
located at the bottom of the enclosure.
The BPM signal lines from the servo gauge terminates on the FCM-
BPM module connector.
FIGURE 4-4 WFI - BPM cable wiring
The BPM cable coming from Gauge must be connected and screwed to
CN2 on FCM-BPM Module. 2 Ferrite beads must be added on the BPM
signal line.
The PE (CN2 – Pin No 4) of FCM-BPM module must be connected to
PE mounting stud.
Mains Input
BPM cable