User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 48 Service Manual
6.4.5.2.5 Configurable Transducer Block Settings
The configurable transducer blocks are special in the way that they do
not represent a fixed input function of the SmartRadar. Configurable
transducer blocks can be programmed to represent any available
functions on any of the available FlexConn boards in the SmartRadar.
NOTE: The configuration of the configurable transducer
blocks must be done using Engauge.
The current firmware version does have some limitations on what can
be programmed in these transducer blocks.
Configurable Transducer block 1 can only represent Levels. This is
valid for both the PV and the SV.
Configurable Transducer block 2 can only represent Temperatures.
This is valid for both the PV as the SV.
Configurable Transducer block 3 can only represent either pressure
or Density. This is valid for both the PV and the SV.
Configurable Transducer block 4 can represent parameters with
variable dimensional units. The following parameters are supported:
Level, Temperature, Pressure, Density, Current, or NO UNIT. This is
valid for both the PV and the SV.
In wireless builder these limitations must be taken into account when
changing the units index, for both the PV as the SV. Selecting a
dimensional unit that is not supported by the Transducer block will give
an error message.
The Units Index for the PV can be found on the Ranges tab.
- Decimal Not used in the SmartRadar FlexLine
Rate of Change Scale:
- EU at 100% Not used in the SmartRadar FlexLine
- EU at 0% Not used in the SmartRadar FlexLine
- Units Index In this field you can select the required engineering unit from the list of available units.
(level units for the level TB, and temperature units for the temperature TB).
Note: For supported units, see 6.4.5.2.8.
- Decimal Not used in the SmartRadar FlexLine
Example
Configurable Transducer block 1 could be programmed to represent
the radar level from the CAN-XBAND. Then the PV of this tranducer
block will represent the PV of the radar level function, the Innage
value. The SV of this transducer block will represent the SV of the
radar level function, the Ullage level.
Parameter Description