User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 108 Service Manual
TABLE 6-2 Accepted HART addresses
Before proceeding with commissioning, first check the maximum
start-up current of all connected HART devices.
Make sure the HART address of the installed device(s) are in
accordance with TABLE 6-2.
6.8.3.2 P1 Pressure
The FCI-HT software only accepts the Primary Value of a P1 pressure
HART device in SI units kilo Pascals (kPa).
Make sure the P1 pressure HART device is configured to output data
in kilo Pascals (kPa). If not, correctly configure as yet, by using an
appropriate HART configuration tool.
TABLE 6-3 Accepted PV unit for a P1 HART device
NOTE: The Secondary and Tertiary values of a P1 pressure
HART device may be any units.
The PV of the P1 pressure HART device is read and converted into SI
Units Pascals (Pa) within the FlexConn function PV.
The value is filtered, and the filtering factor depends on the value set in
the entity
[P1 Integration time]. A higher value gives more filtering, and a
lower value gives less filtering.
05 HART generic sensor
06 HART generic sensor
07 HART generic sensor
08 HART generic sensor
09 HART generic sensor
10 HART generic sensor
11 HART generic sensor
12 HART generic sensor
13 HART generic sensor
14 HART generic sensor
15 HART generic sensor
Sensor Type
Accepted HART
PV Unit
Abbreviation
HART PV Unit
Code
P1 Pressure Kilo Pascal kPa 12
HART Address Function