User Manual

Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 109
The correction factor stored in the [P1 PV offset] entity is then subtracted
from the filtered value. If the
[P1 PV offset] entity = 0 no offset is applied.
Depending on the
[PV selected type] entity, the P1 pressure can be
displayed as either absolute pressure or relative pressure.
TABLE 6-4 P1 pressure displayed unit types
If Relative pressure is selected, the value stored in the
[Ambient Air
Pressure]
entity is added to the measured pressure. If Absolute pressure
is selected, no factor is added. The final result is available in the
[Primary
Value]
entity.
NOTE: Absolute pressure is used in the density calculation;
the relative pressure is only displayed in P1
[Primary
Value]
.
For the FCI-HT software to differentiate between a HART device
malfunction and a HART device not actually installed, P1 pressure has
the entity
[P1 Installed] which must be set to either <Installed> if a P1
pressure HART device is actually fitted or
<Not Installed> if a P1 pressure
HART device is not actually fitted.
The Secondary and Tertiary values of a P1 pressure HART device are
not converted, and they are simply translated from the HART device to
the FlexConn environment.
6.8.3.3 P3 Pressure
The FCI-HT software only accepts the Primary Value of a P3 pressure
HART device in SI units kilo Pascals (kPa).
Make sure the P3 pressure HART device is configured to output data
in kilo Pascals (kPa). If not, correctly configure as yet, by using an
appropriate HART configuration tool.
TABLE 6-5 Accepted PV unit for a P3 HART device
NOTE: The Secondary and Tertiary values of a P3 pressure
HART device may be any units.
PV Unit Type Display Unit Type PV selected type
P1 Pressure Absolute 1
Relative 2
Sensor Type
Accepted HART
PV Unit
Abbreviation
HART PV Unit
Code
P3 Pressure Kilo Pascal kPa 12