Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 114 Service Manual
A HART temperature sensor may have a PV unit code Ohms, and a SV
unit code Celsius. The required sensor value is temperature in Celsius,
and this is translated into the FlexConn PV, and the Ohms value is
translated into the FlexConn SV.
Translation is performed in the order: PV (Distance, Temperature,
Pressure, and Density), SV (Distance, Temperature, Pressure, and
Density), TV (Distance, Temperature, Pressure, and Density).
The required sensor value read from the generic HART devices will be
converted into SI Units within the FlexConn PV as shown in TABLE 6-9.
The other sensor values of a generic HART device are not converted,
and they are simply translated from the HART device environment into
the FlexConn environment SV and TV.
TABLE 6-9 Generic HART device units into FlexConn PV unit translation
6.8.3.6 Function Identification
Functions 1 through 8 are identified by the entities: [Function Category],
[Function Type], and [Function Sub-type].
Their default identification information is detailed in TABLE 6-10.
Accepted HART Units Abbreviation
FlexConn PV
Unit Translation
Abbreviation
Pounds per square inch psi Pascal Pa
Pascal Pa
Kilo Pascal kPa
Degrees Celsius °C Celsius °C
Degrees Fahrenheit °F
Feet ft Meters m
Meters m
Inches in
Kilograms per cubic meter kg/m
3
Kilograms per
cubic meter
kg/m
3
Pounds per cubic foot lb/ft
3
Degrees API API
Function Allocation
Function
Category
Function Type
Function
Sub-type
Function 1 P1 Pressure Sensor (1) Product pressure (5) (6)
Function 2 P3 Pressure Sensor (1) Vapour pressure (13) (7)
Function 3 Distance Sensor (1) HART transmitter (12) (16)