User Manual

Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 117
TABLE 6-13 SmartView displayed unit types
The following PV types are supported on the SmartView display for P1
pressure and P3 pressure only. These are available changed by setting
the [PV selected type] entity. This is detailed in TABLE 6-14.
TABLE 6-14 P1 and P3 pressure displayed unit types
6.8.4 Board Commissioning
The commissioning entity for each function is initially default to <False>.
The commissioning entity for each function will only be
<True> when the
associated entities of each function have been set within normal
operating range.
The board-level commissioned entity default is also
<False>. It will only
be
<True> when all the function-level commissioned entities are <True>.
6.8.4.1 Function 1 Commissioning
Set all Function 1 entities according to TABLE 6-15 requirements, to
commission P1.
Other Milli
<m ...> 1-
(none)
<-> 2-
Kilo
<k ...> 3-
Mega
<M ...> 4-
PV Unit Type
Display Unit
Type
Displayed Type
PV selected
type
P1 Pressure Absolute <ABS> 1
P3 Pressure Relative
<REL> 2
HIMS
Density
P1 Pressure
Sensor
Detected
P1 Ambient Air Pressure and P1 Installed Commissioned
<Enabled> N/A [P1 ambient air pressure] z <default>
AND
[P1 installed] = <enable>
<True>
[P1 ambient air pressure]
= <default>
OR
[P1 installed]= <disable>
<False>
PV Unit
Type
Display Unit
Type
Displayed
Units
PV
Selected
Unit
Range