User Manual

Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 127
Give command [Enter Calibration Mode]
Give command [Calibrate Analog Output at 4mA]
Measure actual output current through the loop resistor, using a
current meter
Enter this value in the
[Analog Output at 4mA] entity
Give command [Calibrate Analog Output at 18mA]
Measure actual output current through the loop resistor, using a
current meter
Enter this value in the [Analog Output at 18mA] entity
Give command [Exit Calibration Mode], to exit the calibration mode
These calibration data are used to calculate the analog output current
for the Primary Value (PV).
Untill calibration has been carried out, the Health status of the PV and
the analog output function will be:
Status
<BAD>
Status Category <STATUS_CATEGORY_BAD_GENERAL_CALIBRATION_FAIL>
Status Code <CALIBRATION_SET_POINTS_NOT_CALIBRATED>