Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 129
6.9.5.2 Commissioning
The following entities must be set by Engauge or SmartView for a
correct functioning of the HCI-HAO module in an instrument.
[PV Lower range value] Lw Range Value Float Non-Volatile <0> Sensor (Analog
Output)
[PV Upper range value] Up Range Value Float Non-Volatile <0>
[Analog Output mode]
HART Mode Enumeration
<Fixed 4-
20mA>
<Standard 4-
20mA>
Non-Volatile <Standard 4-
20mA>
[Burnout Value] Burnout Value Float Non-Volatile <3.6>
[Burnout Behavior]
Burnout Behavior Enumeration
<BAD>
<UNCERTAIN>
<BAD +
UNCERTAIN>
Non-Volatile <BAD>
[Enter Calibration Mode]
Enter Cal Mode Undefined Command
[Cal Value at 4 mA] Cal Value at 4 mA Float Non-Volatile <0>
[Cal Value at 18 mA]
Cal Value at 18 mA Float Non-Volatile <0>
[Calibrate at 4 mA]
Calibrate at 4 mA Undefined Command
[Calibrate at 18 mA] Calibrate at 18 mA Undefined Command
[Exit Calibration Mode] Exit Cal Mode Undefined Command
Name Explanation Default Value
Function
Part
Function
[PV Link board ID] Board ID of Other FlexConn
to be linked as PV to HCI-
HAO
<0> Board Board Specific
[PV Link board instance] Board Instance of the linked
PV board
<0>
[PV Link function instance]
Function Instance of the
linked PV board
<0>
[PV Link Sensor Value]* Primary or secondary
variable of linked card can
be assigned to this
<PV_LINK>
Entity SmartView Display Data Type Type Default Function