User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 138 Service Manual
6.10.3.1.1 Product Temperature
The following entities must be set by Engauge or SmartView for a
correct functioning of the FII-VT module in an instrument.
NOTE: Using Engauge, following entities are set within the
Engauge Product temperature tab.
The following entities can be set by Engauge or SmartView for a correct
functioning of the FII-VT module in an instrument.
Check each entity for its correctness.
Name Explanation Value Range Default
[Lowest element offset] The distance from tank zero
till the lowest element
position in the temperature
probe
floating point number:
<-x.x .. +x.x>
<80.0>
[Sensor length]
The distance from the
Pt100 position till the
highest element position
floating point number:
<-x.x .. +x.x>
<80.0>
Name Explanation Value Range Default
[Product immersion depth] The minimum required
distance of the product
level above an element
before it is taken into
account in the average
product temperature
calculation
floating point number:
<-x.x .. +x.x>
<0.5>
[Hysteresis]
The distance for a
hysteresis mechanism
around the switching point
of the elements that are
taken into account in the
calculation
floating point number:
<-x.x .. +x.x>
<0.1>
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
4 thresholds for activating a
related alarm status in the
Primary Value
floating point number:
<-x.x .. +x.x>
<+1.0E22>