Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 140 Service Manual
6.10.3.1.3 Water Level (for 766/768 Combi probes and 765 Water probe only)
The following entities must be set by Engauge or SmartView for a
correct functioning of the FII-VT module in an instrument.
[Alarm test enable] Enables (if activated, see
next listed entity) the
simulation of one of the 4
alarms for a minute, by
simulating the actual
measured Primary Value is
below or above the alarm
threshold.
<enable>
<disable>
<disable>
[Alarm test]
Activates and selects at the
same time the Alarm test (if
enabled with the [Alarm test
enable]
listed before, and the
4 alarm thresholds are
properly set).
[No Alarm]
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
<No Alarm>
[Function identification]
The current module’s
function name. This
function is visible on the
SmartView display.
13 characters
<Vapour temp.>
Name Explanation Value Range Default
[Maximum water capacity] The maximum capacity
when the probe is fully
submerged in water (in pF)
floating point number:
<-x.x .. +x.x>
<20000>
[Minimum water capacity]
The minimum capacity
when the probe is not
submerged in water (in pF)
floating point number:
<-x.x .. +x.x>
<20000>
[Water probe bottom position]
The offset to the water
probe zero point in relation
with the tank zero point
floating point number:
<-x.x .. +x.x>
<80>
[Upper reference level]
The distance from tank zero
point to upper reference
point; is used for water
ullage calculation
floating point number:
<-x.x .. +x.x>
<80>
Name Explanation Value Range Default