User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 146 Service Manual
The following entities can be set by Engauge or SmartView for a correct
functioning of the FII-VT module in an instrument.
Check each entity for its correctness.
Name Explanation Value Range Default
[Product immersion depth] The minimum required
product level distance
above an element before
this element is taken into
account in the average
product temperature
calculation
floating point number:
<-x.x .. +x.x>
<0.5>
[Hysteresis]
This is a hysteresis
mechanism distance
around the switching points
of the elements that are
taken into account in the
calculation.
floating point number:
<-x.x .. +x.x>
<0.1>
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
4 thresholds for activating a
related alarm status in the
Primary Value
floating point numbers:
<-x.x .. +x.x>
<1.0E22>
[Alarm test enable] Enables (if activated, see
next listed entity) the
simulation of one of the 4
alarms for a minute, by
simulating the actual
measured Primary Value is
below or above the alarm
threshold.
<enable>
<disable>
<disable>
[Alarm test]
Activates and selects at the
same time the Alarm test (if
enabled with the
[Alarm test
enable]
listed before, and the
4 alarm thresholds are
properly set).
[No Alarm]
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
<No Alarm>
[Function identification]
The current module’s
function name. This
function is visible on the
SmartView display.
13 characters <Product temp.>