6.10.3.3.1 Water Level
The following entities must be set by Engauge or SmartView for a
correct functioning of the FII-VT module in an instrument.
The following entities can be set by Engauge or SmartView for a
correct functioning of the FII-VT module in an instrument.
Name Explanation Value Range Default
[Maximum water capacity] The maximum capacity
when the probe is fully
submerged in water (in pF)
floating point number:
<-x.x .. +x.x>
<20000>
[Minimum water capacity]
The minimum capacity
when the probe is not
submerged in water (in pF)
floating point number:
<-x.x .. +x.x>
<20000>
[Water probe bottom position] The offset to the water
probe zero point in relation
with the tank zero point
floating point number:
<-x.x .. +x.x>
<80>
[Upper reference level] The distance from tank zero
point to upper reference
point; is used for water
ullage calculation
floating point number:
<-x.x .. +x.x>
<80>
Name Explanation Value Range Default
[Water probe length] The length of the 765 VITO
water probe
floating point number:
<-x.x .. +x.x>
<0.5>
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
4 thresholds for activating a
related alarm status in the
Primary Value
floating point numbers:
<-x.x .. +x.x>
<+1.0E22>
[Alarm test enable]
Enables (if activated, see
next listed entity) the
simulation of one of the 4
alarms for a minute, by
simulating the actual
measured Primary Value is
below or above the alarm
threshold.
<enable>
<disable>
<disable>