User Manual

Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 155
W&M Sealing
1
: This board can be electronically sealed via the
software. A Notified Body can set his password via
[W&M notified body
seal password]
. He can apply the seal by setting [W&M seal]. Here some
data logging is filled in and the related password. This requires a
W&M module for Engauge.
If the primary value of the product temperature is completely valid,
then a W&M indication will be set (e.g. visible in SmartView).
Unsealing: give the
[W&M unseal level 1] and [W&M unseal the level 2]
commands successively.
History can be made visible via
[W&M seal history].
6.11.4 Commissioning
6.11.4.1 Commissioning Parameters for 1 or 2 RTDs (3- and 4-wire) Temperature Calcula-
tions
NOTE: Make sure the RTD/MPT jumper is set to RTD.
The following entities must be set set by Engauge or SmartView for
a correct functioning of the FII-RTD module in an instrument. The
default values are available after initialization of the non-volatile
memory.
1. Weights & Measures Sealing.
Name Explanation Value Range Default
[Lowest element offset] The distance from tank zero
till the first RTD
floating point number:
<-x.x .. +x.x>
<80.0>
[Second element offset]
if applicable
The distance from tank zero
till the second RTD
floating point number:
<-x.x .. +x.x>
<0.0>
[Number of elements] The number of RTDs used <1..2> <0>
[Element type] The type (material) of the
used RTDs
<Pt100 large + small>
<Ni191>
<PtCu100>
<Cu100>
<Cu90 enraf + beacon + weston/
solartron/nulectrohms>
<Sangamo MRT>
<Sangamo spot>
<No type>
[Measurement type]
Selects RTDs, MPT, or
MRT.
<RTD 3wire>
<RTD 4wire>
<MPT>
<MRT>
<No type>