User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 156 Service Manual
6.11.4.2 Commissioning Parameters for MPT Temperature Calculations
NOTE: Make sure the RTD/MPT jumper is set to MPT.
The following entities must be set set by Engauge or SmartView for
a correct functioning of the FII-RTD module in an instrument. The
default values are available after initialization of the non-volatile
memory.
6.11.4.3 Commissioning Parameters for MRT Temperature Calculations
NOTE: Make sure the RTD/MPT jumper is set to MRT
(= MPT position).
The following entities must be set set by Engauge or SmartView for
a correct functioning of the FII-RTD module in an instrument. The
default values are available after initialization of the non-volatile
memory.
[RTD configuration] Selects how the RTDs are
positioned.
<RTD1 in tank>
<RTD1 and RTD2 in tank>
<RTD1 in tank and RTD2
ambient> <RTD1 ambient>
<No configuration>
Name Explanation Value Range Default
[Lowest element offset] The distance from tank zero
till the bottom of the probe
floating point number:
<-x.x .. +x.x>
<80.0>
[Number of elements] The number of elements
used
<1..6> <0>
[Element type] The type (material) of the
used RTDs
<Pt100 large + small>
<Ni191>
<PtCu100>
<Cu100>
<Cu90 enraf + beacon + weston/
solartron/nulectrohms>
<Sangamo MRT>
<Sangamo spot>
<No type>
[Measurement type]
Selects RTDs, MPT, or
MRT.
<RTD 3wire>
<RTD 4wire>
<MPT>
<MRT>
<No type>
[MPT sensor length]
The length of the MPT
probe
floating point number:
<-x.x .. +x.x>
<80.0>
Name Explanation Value Range Default