User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 158 Service Manual
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
4 thresholds for activating a
related alarm status in the
Primary Value
floating point numbers:
<-x.x .. +x.x>
<1.0E22>
[Alarm test enable] Enables (if activated, see
next listed entity) the
simulation of one of the 4
alarms for a minute, by
simulating the actual
measured Primary Value is
slightly below or above the
alarm threshold.
<enable>
<disable>
<disable>
[Alarm test] Activates and selects at the
same time the Alarm test (if
enabled with the
[Alarm test
enable]
listed before, and the
4 alarm thresholds are
properly set).
<No Alarm>
<High High alarm>
<High Alarm>
<Low Alarm>
<Low Low alarm>
<No Alarm>
[Function identification]
The current module’s
function name. This
function is visible on the
SmartView display.
13 characters
<Product temp.>
[Element offset]
Each element can
individually be given an
offset.
floating point numbers:
<-x.x .. +x.x>
<0.0>
[Element weighing factor]
Each element can
individually be given a
weighing factor, which is
applicable if the calculation
method is CUSTOM.
floating point numbers:
<-x.x .. +x.x>
<1.0>
[Gauge temperature scale]
Determines whether the
IPTS-68 or ITS-90 scale is
used.
<IPTS-68>
<ITS-90>
<ITS-90>
[Low element usage] See FIGURE 6-42 <No Exclusion>
<Static Exclusion>
<Dynamic Exclusion>
<No Exclusion>
[Low element behaviour] See FIGURE 6-42 <Temp To Fail>
<Temp To Last Valid>
<Temp Use First Element>
<Temp Use Second Element>
<Temp To Fail>
[Temperature element exclude
zone]
See FIGURE 6-42 floating point number:
<-x.x .. +x.x>
<1.0>
Name Explanation Value Range Default