User Manual

Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 3
The HCI-BPM module supports 2 protocols:
The Enraf GPU protocol with its records and items (limited);
The Enraf FlexConn protocol with its so-called entities.
The module can communicate with:
880 CIU prime
858 CIU
780 SmartLink
6.2.2 Commissioning the HCI-BPM
For a correct functioning of the HCI-BPM module within an instrument
(gauge), the following entities can be set by using either Engauge or
SmartView.
By using the following table, check each entity for correctness.
Name Value Range Default Value Explanation
[Baudrate] <1200>
<2400>
<4800>
<1200>
Communication speed
[BPM sensitivity] <1..8> <8> The sensitivity of the
receiver circuit
1 = weakest
8 = strongest
[Identification] 8 characters e.g.
<TANK1234>
<-------->
Name of a tank or
instrument
[GPU instrument address] <0..99> <0> The address of this
instrument for GPU
messages.
Note: Each instrument must
have a unique GPU
address.
[FlexConn instrument address] <0..1899> <0> The address of this
instrument for FlexConn
messages.
Note: Each instrument must
have a unique FlexConn
address.
[Level units] <meters>
<inches>
<feet>
<fractions>
<meters> The unit in which level-
related GPU records and
items are shown
[Temperature units] <celsius>
<fahrenheit>
<celsius> The unit in which
temperature-related GPU
records and items are
shown