Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 10 Service Manual
The register data in the response message is packed as two
bytes:
The amount of bytes N is double the amount of requested
registers, because each register occupies two bytes.
Function code 05 Write single coil
Coils are located in the memory range (0)0000 ... (0) FFFFH. The
value of a coil can be forced to: FF00H = ON, or 0000H = OFF.
The query message specifies the coil reference to be forced:
The normal response is an echo of the query, returned after the
coil state has been forced:
6.3.3.3 Commisioning Notes
While commissioning, please keep the following in mind:
For gauge configuration --> FlexConn must be used.
For data monitoring and certain gauge commands--> Modbus
can be used.
Slave
address
Function 03
Byte count
(N)
Data CRC check
8 bits 8 bits 8 bits (N) x 8 bits 16 bits
Slave
address
Function 05
Coil
address
Force data CRC check
8 bits 8 bits 16 bits 16 bits 16 bits
Slave
address
Function 05
Coil
address
Force data CRC check
8 bits 8 bits 16 bits 16 bits 16 bits