User Manual

Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 31
6.3.3.6.12 Overfill Protection Status
For a listing of ASCII codes, see 6.3.4.
6.3.3.6.13 Alarms
6.3.3.6.14 Gauge Status
The following table lists the Gauge status information and meaning.
2835 TRANSDUCER_SERIAL_NUMBER_NOT_SET
2836 UNABLE_TO_GET_LINKED_VARIABLE
2837 UPPER_RANGE_VALUE_GREATER_THAN_UPPER_TRANSDUCER_
LIMIT
2838 LOWER_RANGE_VALUE_LESS_THAN_LOWER_TRANSDUCER_LIMIT
Overfill Protection status Meaning
O Overfill
W Warning
HHealthy
Product Level Alarm status Meaning
0 no alarm
1 Low level product alarm tripped
2 High level product alarm tripped
3 Low low level product alarm tripped
4 High high level product alarm tripped
255 alarm failure
Gauge status (decimal) Meaning
0 Level gauge is measuring level
255 Level gauge is in failure
Health
status
code
Meaning