Install Instructions
Table Of Contents
802360 REPLACEMENT MOTORS
© 2020 Resideo Technologies, Inc. All rights reserved.
The Honeywell Home trademark is used under license from Honeywell International, Inc. This product is manufactured by Resideo Technologies, Inc. and its affiliates.
www.resideo.com
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
69-0481—04 M.S. Rev. 03-20 | Printed in United States
Fig. 2. Replace powerhead motor.
CHECKOUT
1. Raise the set point on the zone thermostat
about 10° F [6° C] above room temperature to
initiate a call for heat.
2. Observe all control devices—the valve should
open and the auxiliary switch should make the
circuit to the circulator or other valve at the end
of the opening stroke.
3. Lower the set point on the zone thermostat
about 10° F [6° C] below room temperature.
4. Observe the control devices—the valve should
close and auxiliary equipment should stop.
The valve should run smoothly and positively
from closed to open to closed position.
M8121A
FIT TAB
UNDER SLOT
MOTOR
LEADS (2)
CUT AND
SPLICE
WIRES
HERE
AUX. SWITCH
LEADS (2)
MOTOR