Owner's Manual
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
39 68-0312—03
408 Max. Cool
Recovery Ramp
Rate
Off
1° F/hr to 20° F/hr
6° F/hr Commercial No Off: The cooling system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is
set, the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Maximum Recovery Ramp Rate based
on the rate that the cooling system can
recover at for a mild day in your region.
Default setting is 6° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region to
be associated with the Maximum Recovery
Ramp Rate.
The thermostat will begin recovery at the
optimal time based on a calculated ramp rate,
allowing the system to recover on time and
save energy during changing outdoor
conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature.
408 Max. Cool
Recovery Outdoor
Temp
Off
-20° F to 100°F
70° F Commercial No Off: The cooling system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is
set, the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Maximum Recovery Ramp Rate based
on the rate that the cooling system can
recover at for a mild day in your region.
Default setting is 6° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region to
be associated with the Maximum Recovery
Ramp Rate.
The thermostat will begin recovery at the
optimal time based on a calculated ramp rate,
allowing the system to recover on time and
save energy during changing outdoor
conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes