Owner's Manual

Table Of Contents
VISIONPRO
®
8000 WITH REDLINK™
68-0312—03 54
1012 Vent Priority
Lockouts
ASHRAE
Lockouts Residential No Lockouts are Priority: The thermostat places
a priority on lockouts versus the ASHRAE 62.2
ventilation standard. The thermostat will not
run ventilation during the following lockout
conditions (if configured) unless you
manually call for ventilation:
Lockout Ventilation during Outdoor Conditions
(ISU 1013)
Lockout Ventilation on Humidification or
Dehumidification Calls (ISU 1014)
Lockout Ventilation during “Sleep” (Residential)
or “Unoccupied” (Commercial) program
periods. Note: This option is set by the user on
the Ventilation screen in the Menu.
ASHRAE is Priority: ASHRAE requires
additional ventilation following a long off
cycle. The thermostat meets the ASHRAE 62.2
ventilation standard by running additional
ventilation when outdoor conditions are
favorable. If ASHRAE cannot be met when
outdoor conditions are favorable, the
thermostat will override the outdoor lockouts
and run ventilation. When using this option, it
is recommended to increase the rate (CFM) of
the ventilation equipment to meet the ASHRAE
62.2 ventilation standard in a shorter run time.
Notes:
ISU 1014 Lockout Ventilation on Humidification
or Dehumidification calls is not an option when
you select ASHRAE is Priority.
The ability to lockout ventilation during the
“Sleep” or Unoccupied program periods is not
an option when you select ASHRAE is Priority.
1013 Low Outdoor
Temp Vent
Lockout
Off
-20° F to 40° F (in 5° F
increments)
Off Both No Requires an outdoor sensor.
This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See “Ventilation — Outdoor Condition
Lockouts (ISU 1013)” beginning on page 91.
1013 High Outdoor
Temp Vent
Lockout
Off
80° F to 110° F (in 5° F
increments)
Off Both No Requires an outdoor sensor.
This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See “Ventilation — Outdoor Condition
Lockouts (ISU 1013)” beginning on page 91.
1013 High Out. Dew
Point Vent
Lockout
Off
65° F to 85° F (in 5° F increments)
Off Both No Requires a Wireless Outdoor Sensor (sense
outdoor humidity).
This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See “Ventilation — Outdoor Condition
Lockouts (ISU 1013)” beginning on page 91.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes