Owner's Manual
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
68-0312—03 54
1012 Vent Priority
Lockouts
ASHRAE
Lockouts Residential No Lockouts are Priority: The thermostat places
a priority on lockouts versus the ASHRAE 62.2
ventilation standard. The thermostat will not
run ventilation during the following lockout
conditions (if configured) unless you
manually call for ventilation:
• Lockout Ventilation during Outdoor Conditions
(ISU 1013)
• Lockout Ventilation on Humidification or
Dehumidification Calls (ISU 1014)
• Lockout Ventilation during “Sleep” (Residential)
or “Unoccupied” (Commercial) program
periods. Note: This option is set by the user on
the Ventilation screen in the Menu.
ASHRAE is Priority: ASHRAE requires
additional ventilation following a long off
cycle. The thermostat meets the ASHRAE 62.2
ventilation standard by running additional
ventilation when outdoor conditions are
favorable. If ASHRAE cannot be met when
outdoor conditions are favorable, the
thermostat will override the outdoor lockouts
and run ventilation. When using this option, it
is recommended to increase the rate (CFM) of
the ventilation equipment to meet the ASHRAE
62.2 ventilation standard in a shorter run time.
Notes:
• ISU 1014 Lockout Ventilation on Humidification
or Dehumidification calls is not an option when
you select ASHRAE is Priority.
• The ability to lockout ventilation during the
“Sleep” or Unoccupied program periods is not
an option when you select ASHRAE is Priority.
1013 Low Outdoor
Temp Vent
Lockout
Off
-20° F to 40° F (in 5° F
increments)
Off Both No Requires an outdoor sensor.
This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See “Ventilation — Outdoor Condition
Lockouts (ISU 1013)” beginning on page 91.
1013 High Outdoor
Temp Vent
Lockout
Off
80° F to 110° F (in 5° F
increments)
Off Both No Requires an outdoor sensor.
This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See “Ventilation — Outdoor Condition
Lockouts (ISU 1013)” beginning on page 91.
1013 High Out. Dew
Point Vent
Lockout
Off
65° F to 85° F (in 5° F increments)
Off Both No Requires a Wireless Outdoor Sensor (sense
outdoor humidity).
This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See “Ventilation — Outdoor Condition
Lockouts (ISU 1013)” beginning on page 91.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes