V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES
60-2133—9
6
Approvals:
Underwriters Laboratories Inc. Listed: V4043A,B,E;
V4044A,B; V8043A,B,E,J; V8044A,B,E: File MH11826, Vol.
1, dated 2-22-88.
Replacement Parts:
Motor Part Numbers (use with V4043, V4044, V8043,
V8044):
802360JA 24 Vac, 60 Hz, Class A, plated.
802360LA 120 Vac, 60 Hz, Class F, plated.
802360MA 208 Vac, 60 Hz, Class F, plated.
802360NA 220V 50 Hz, 240V 60 Hz, Class F, plated.
802360UA 24 Vac, 60 Hz, Class F, plated.
Powerhead (see Table 2):
Includes motor, housing and two mounting screws.
Flow Capacity
Rating
Maximum
Closeoff Pressure
Max Fluid Min Fluid Max Ambient
Valve Family Cv kV psi kPa
Temperature Temperature Temperature
V4043A,B,E,J 1.0 .86 50 345 240°F (116°C) 40°F (5°C) 125°F (50°C)
3.5 3.0 20 138 240°F (116°C) 40°F (5°C) 125°F (50°C)
10.0 8.6 6.5 45 240°F (116°C) 40°F (5°C) 125°F (50°C)
V8043A,B,E,F 3.5 3.0 20 138 200°F (93°C) 40°F (5°C) 125°F (50°C)
8.0 7.0 8 55 200°F (93°C) 40°F (5°C) 125°F (50°C)
10.0 8.6 6.5 45 200°F (93°C) 40°F (5°C) 125°F (50°C)
V4044A,B 4.0 3.4 20 138 240°F (116°C) 40°F (5°C) 125°F (50°C)
7.0 6.0 10 69 240°F (116°C) 40°F (5°C) 125°F (50°C)
V8044A,B,E 4.0 3.4 20 138 200°F (93°C) 40°F (5°C) 125°F (50°C)
7.0 6.0 10 69 200°F (93°C) 40°F (5°C) 125°F (50°C)
V4043E, V8043J (steam) 15
a
103 240°F (116°C) 40°F (5°C) 125°F (50°C)
Static Pressure Rating of 125 psi (862 kPa) applies to all valves.
a
15 psi low pressure steam.
Conversion Kits:
Conversion kits for converting old style (series 1-5) valve
bodies to accept 40003916 Powerhead (use with V4043,
V4044, V8043, V8044). Includes metal plate with driveshaft
and rubber ball, O-Ring and four screws.
Two-way water valve body: 40003918-006.
Three-way water valve body: 40003918-007.
Two-way steam valve body: 40003918-008.
O-Ring Part Numbers:
272742A—Includes replacement ball plug, large O-Ring
and four screws.
272756A—Package of five large O-Rings.
Accessories:
803867A Conduit Cover: Includes 803858 Cover and
803859 Case (for V8043F).
Flow and Temperature Ratings:
Flow Capacity
Rating
Pipe
Connections
Model
Control
Circuit Cv kV Wire Hookup Type
Size
(in.)
Valve
Body
De-energized
Position
V8044B 24V, 60 Hz
b
4.0 3.4 18 in. (457 mm) leadwires,
1/2 in. conduit opening.
Sweat 1/2 2-position
diverting
Port A Normally
Closed
V8044E 24V, 60 Hz 4.0 3.4 18 in. (457 mm) leadwires
and end switch, 1/2 in.
conduit opening.
Sweat 1/2 2-position
diverting
Port A Normally
Closed
24V, 60 Hz 7.0 6.0 Sweat 3/4
a
30 in. (762 mm) leads also available.
b
Includes integral changeover Aquastat® Control.
c
96 in. (2438 mm) leads also available.
d
30 in. (762 mm) leads also available.
e
Valve available with reduced (2.5 C
v
[2.1 kV] ) rating on bypass port. Sweat fitting only.