INSTALLATION INSTRUCTIONS
Put Bar Code Here
95C-10920-03
VC2, VC4, VC60, VC8
ON-OFF ACTUATOR FOR VC SERIES BALANCED 
HYDRONIC VALVES
These 2-position (open/close) control actuators are used with 
VCZ1000, 1100, 6000 and 6100 series hydronic valves in a 
normal indoor environment to provide quick opening/closing to 
control the flow of hot and/or chilled water or glycol solution to 
60% concentration. They are designed for on-off "zone" 
control of heating/cooling systems, or to control individual fan 
coil, baseboard radiator or convector applications.
Depending on the model selected, the actuator can be 
controlled by a low or line voltage SPST or SPDT controller, 
such as a room thermostat, aquastat or flow switch. 
VC80 series valve actuators are designed to be used with 
hard-wired electronic thermostats with series anticipator or 
power-stealing thermostats. Recommended control 
thermostats include T8601D, T8401C,T8380 and T8360 
families. 
VC actuators use cam-operated cartridge travel to resist water 
hammer. Internal limit switches prevent motor overrun.
SPECIFICATIONS
The specifications following are nominal and conform to 
generally acceptable industry standards. Honeywell is not 
responsible for damages resulting from misapplication or 
misuse of its products
Supply Voltage: Colour coded label  
24V, 50Hz Model Blue
24V, 60Hz Model Blue 
100-130V, 50-60Hz Model Black
200-240V, 50-60Hz Model Red
Power consumption: 6 Watts Max. at nominal Voltage (dur-
ing valve position change). Use 24 V Class 2 transformer 
and provide 6 VA for transformer and connection wire siz-
ing.
Maximum Duty Cycle: 15%
Nominal timing: 
Valve opens in 6 seconds @ 60Hz (20% longer @ 50Hz).
VC8040 Series opens in 12 seconds @ 60Hz (20% longer @ 
50Hz).
Electrical termination: 3 versions available: 
(1) Molex™ (header # 39-30-1060). Requires mating connec-
tor (receptacle/housing # 39-01-2060). OR 
(2) With integral 1 meter [nominal 39"] leadwire cable. OR
(3) With 5 feet (1.5 meter) plenum-rated leadwire cable per 
UL94-5V. Includes plastic adapter for use with 3/8” flexible 
conduit.
End Switch Rating:
2.2 A inductive from 5 to 110 Vac,
1.0 A inductive above 110 to 277 Vac.
Min. DC switching capability: 5mA @ 24 Vdc.
Operating ambient temperature: 0 to 65°C [32 to 150°F] 
Except VC2114, VC2714, VC8114 & VC8714 are 0 to 60°C 
[32 to 140°F]
Humidity Rating: 5-95% RH (non-condensing)
Fluid temperatures: 1 to 95° C [34 to 203° F]
Shipping & storage temperature:  -40 to +65°C [-40 to 
+150°F]
Atmosphere: 
Non-corrosive, non-explosive.
Nominal Dimensions (Actuator Only):
3-23/32" width x 2-11/16" depth x 2-3/4" height 
94 mm width x 68 mm depth x 70 mm height
Accessories: 272866B Valve Flushing Cap
Models:
Actuator Only: VC2, VC4, VC60, VC8 (See Table 1)
Bodies (Order Separately): VCZ... (See 95C-10919)