Product Overview

PRODUCT DATA
Put Bar Code Here
95C-10909-03
VC6936
NO/NC FLOATING CARTRIDGE/CAGE VALVE WITH POWER
FAILURE REPOSITION
The VC6936 Fail Safe Floating Control Valve provides
proportional control of hot or chilled water in commercial
heating and cooling applications, such as unit ventilators. On
a power failure, this patented actuator design drives the valve
to the fail safe position, either fully open or closed according to
the installer’s wiring connections.
The VC6936 uses a microprocessor-controlled, low voltage
stepper motor with a supercapacitor-based power supply
capable of storing enough power to drive the valve to its fail
safe position when 24V power is removed from the actuator.
The VC hydronic valve consists of a valve body and
replaceable characterized cartridge assembly. When used
with a Honeywell VC6900 or VC7900-series actuator, the
valve provides proportional flow control. Three-way bodies
may use cam-operated cartridge travel to resist water
hammer. Limit switches prevent motor overrun.
SPECIFICATIONS
The specifications following are nominal and conform to
generally accepted industry standards. Honeywell is not
responsible for damages resulting from misapplication or
misuse of its products.
Power:
24V, 50-60Hz; 12W. Class 2 circuit
18 VA maximum (during start up).
Control Signal: 24 Vac, 1.5mA Floating Signal (two mutually-
exclusive momentary contacts for open and close, with
minimum 0.5 seconds on and off timing.)
Annunciation: red LED on cable end.
Nominal Control timing: 120 seconds full stroke
Electrical termination: 5 feet (1.5 m) plenum-rated cable
per UL94-5V. Flexible conduit clamp (3/8”) included.
Operating ambient temperature: 0 to 60 °C (32 to 140 °F)
5-95% RH (non-condensing)
Shipping & storage temperature: -40 to +65 °C (-40 to
+150 °F)
Atmosphere: Non-corrosive, non-explosive.
Approvals:
UL (plenum rating), CE (pending)
FCC Part 15 Class B
Fluid temperatures: 1 to 95 °C (34 to 203 °F)
Pressure rating:
Static – 20 Bar (300 psi)
Burst – 100 Bar (1500 psi)
Operating pressure differential & close-off: Max. – 4 Bar
(60 psi)
Stem Travel: 10 mm (0.4 inches)
Flow Characteristics: Linear or equal percentage, per
Table 2.
Models:
Actuator: VC6936ZZ11
Bodies: VCZ..., per table 2.
Fig. 1. Nominal Dimensions in inches and millimeters
Table 1. Series 60, 24 Vac Actuator
Model
Series
Voltage
(50/60 Hz)
Nominal Stroke
Timing
Electrical
Connection
VC6936 24 Vac 120 seconds. Fail
Safe: 12 Seconds
5’ (1.5 m) plenum-
rated cable