FAN COIL VALVES AND ACTUATORS 
How to Find Valve Pressure Drop 
SI (metric) units (Fig.3) 
1. Calculate desired flow through valve in m
3
/h or litres/ 
second. L/s = 3.6 X m
3
/h. 
2. Determine the k
v
 rating of the valve. 
3. Select the graph corresponding to the k
v
 rating. 
4.  Determine the pressure drop across the valve by: 
1. Locate the flow rate (in m
3
/h on the left edge of the 
graph). 
2. Draw a line from the flow rate to the intersection of 
the k
v
 line. 
3. Draw a line from the intersection to the bottom to 
determine the pressure drop in kPa or Bar. 
1 
10 
1  3  5  30  50  3001 0  1 0 0 
Pressure Drop 
21 
18 
10.8 
7.1 
3.6 
2.2 
1.1 
0.9 
0.7 
0.4 
0.3 
0.5 
3 
5 
0.1 
Flow (L/s)
Flow(m/h)
3 
kPa 
0.01  0.1  1.0
Bar 
36 
kv3.0
kv3.4 
kv7.0 
kv0.8 
kv6.0 
Fig. 3. Flow characteristics of VU53, VU54 valves, SI units. 
INSTALLATION 
When Installing this Product… 
1. Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous 
condition. 
2. Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application. 
3. Installer must be a trained, experienced service 
technician. 
4. After installation is complete, check out product 
operation as provided in these instructions. 
CAUTION 
1.  Disconnect power supply before connecting 
wiring to prevent electrical shock or equipment 
damage. 
2.  On 24V systems, never jumper the valve coil 
terminals even temporarily. This can burn out the 
heat anticipator in the thermostat. 
3.  Wear safety glasses to protect eyes from 
injury when removing or installing the large 
spring clip that holds the actuator mounting 
plate to the valve body. 
Mounting 
The valve can be mounted in any position on a vertical line. 
See Fig. 5. If the valve is mounted horizontally; the actuator 
must be even with or above the center line of the piping. 
Make sure to leave enough room above the actuator to 
remove the cover or actuator for servicing. 
Mount the valve directly in the tube or pipe. Make sure that 
the flow through the valve is in the direction indicated by 
the arrow stamped on the valve body. 
Fig. 5 Mounting positions. 
M10162 
VERTICAL 
PIPING 
HORIZONTIAL 
PIPING 
Use proper snap ring pliers to remove or 
install spring clip. 
95C-10885 