User Guide
Table Of Contents
VU53F,N,S,T; VU54F,N,S,T; VU443A; VU444A; VU843A; VU844A  
FAN COIL VALVES AND ACTUATORS 
On diverting valves, the three fittings or ports are labeled on 
the bottom of the valve body casting. Port AB is the inlet port 
and is open at all times. Port A is closed and port B is open 
when the valve is de-energized. Refer to the equipment 
manufacturer instructions to determine which port (A or B) 
should be connected to the coil bypass. 
Sweat Copper Models 
1.  Use new, properly reamed pipe, free from dents or 
corrosion. 
2.  Place the valve on the pipe. Rotate valve stem so that 
the shaft slot points at the notch in the side of the body 
(90° to flow directions.) See Fig. 6. This protects the 
plug inside the valve by removing it from the seat. 
3.  Sweat the joints, keeping the outer surface free from 
solder. DO NOT use silver solder because of the high 
melting temperature required. 
SHAFT SLOT IN VALVE STEM 
POINTING TO NOTCH ON SIDE OF 
VALVE BODY 
NOTCH 
REMOVING ACTUATOR FROM THE VU-SERIES VALVE 
BODY ASSEMBLY (See Fig. 8): 
Fig. 7 Installing new actuator. 
ENSURE SHAFT 
SLOT 
POINTS TOWARDS 
NOTCH ON SIDE 
OF BODY FOR 
FITTING INTO 
ENGAGING SHAFT 
ACTUATOR 
COUPLING 
NOTCH 
Fig. 6 Slot position. 
To Install & Remove Actuator 
INSTALLING ACTUATOR ON VU-SERIES VALVE 
BODY ASSEMBLY(See Gig. 7) : 
1. 
Orient slot in shaft of VU-series valve body toward
 notch in side of body (i.e. 90
°
 to water flow.) See Fig. 7
.
 This lifts the ball off seat, prevents damage to the ball seat
 while soldering, and makes actuator attachment easier. 
2. Install valve body into pipe. 
3. Wiring connections may be made either before or after
 actuator installed on valve body. 
4. 
Place manual operating lever on the actuator in
 the MAN. OPEN position. 
5. Line up motor coupling to slot in shaft of body and fit the
 head onto the valve body, ensuring that the shaft seats 
correctly. (See Fig. 7) 
6. Snap actuator onto body by pressing down. 
7. Make wiring connections. Refer to wiring section for proper 
instructions. 
Inspect the actuator installation and the valve body to 
ensure that all connections and adjustments have been 
correctly made.  Adjust the thermostat or controller 
connected to the valve so that the valve runs through its 
cycle.  Make sure the valve runs smoothly and positively 
from closed to open to closed again. 
2. 
DEPRESS 
3. LIFT ACTUATOR 
1. PLACE MANUAL 
AUTO  OPEN 
Fig. 8  Removing actuator from valve 
95C-10885
5 